UEEEL0003 — Arrange circuits, control and protection for electrical installations
Generate a complete, audit-ready assessment tool for this unit in minutes: candidate assessment, assessor guide with model answers, and a coverage matrix mapped to every component below. Reviewed and approved by your qualified person, exported under your branding.
Every new account includes a free credit — no card, no subscription.
What an assessment for UEEEL0003 must cover
134 assessable components: 3 elements (12 performance criteria), 25 performance evidence and 97 knowledge evidence requirements. An audit-defensible tool maps every question and task back to these — that mapping is the coverage matrix Auditori generates alongside the assessment.
Elements & performance criteria
1 Prepare electrical circuits, control and protection installation
- 1.1The extent and nature of the electrical installation is determined from job specifications
- 1.2Hazards are identified, risks are assessed and control measures are implemented
- 1.3Load requirements for individual current-using equipment is determined from job specifications and/or consultation with appropriate persons
2 Arrange electrical circuits, control and protection
- 2.1Circuits, control and protective devices are arranged to ensure safe and functional operation of the installation and to comply with relevant industry technical standards and job specification requirements
- 2.2Earthing is arranged and terminated to comply with the multiple earthed neutral (MEN) system requirements
- 2.3Protective devices are selected to meet the required switching and tripping currents coordination and discrimination for overload and short circuit protection in accordance with relevant industry technical standards
- 2.4Residual current devices (RCDs) are selected to meet the required circuit switching and tripping currents, in accordance with relevant industry technical standards
- 2.5Switchgear/control gear is selected to meet current and voltage requirements and confirmed suitable for environmental conditions (ingress protection (IP) ratings) and functional requirements
- 2.6Switchboards are arranged to accommodate control and protective devices, links, safety services and other distributor equipment in accordance with relevant industry technical standards
3 Document electrical installation circuits, control and protection arrangements
- 3.1Evidence is obtained from manufacturer/suppliers that electrical equipment selected complies with safety requirements in accordance with workplace procedures
- 3.2Device selection/s rationale and calculations are documented in accordance with workplace procedures
- 3.3Electrical installation and specifications for selected items are documented in accordance with workplace procedures and forwarded to appropriate person/s
Performance evidence
- # determining the extent and nature of the installation from job specifications
- # arranging the control and protection for electrical installations with and without safety services
- arranging, testing and terminating a multiple earthed neutral (MEN) earthing system
- # applying relevant work health and safety (WHS)/occupational health and safety (OHS) requirements and workplace procedures and practices
- # applying safety principles for electrical systems in buildings and premises
- # applying sustainable energy principles and practices
- calculating prospective fault current in accordance with minimum fault levels specified by local supply authority
- calculating earth fault-loop impedance
- dealing with unplanned events/situations in accordance with workplace procedures in a manner that minimises risk to personnel and equipment
- determining requirements for discrimination and back-up protection for coordination of protection devices
- # determining individual load requirements
- # arranging and terminating circuits, control and protective devices to comply with requirements
- # selecting circuit protective devices and residual current devices (RCDs) that comply with all requirements
- # selecting minimum size-earthing conductors in accordance with relevant industry standards
- selecting circuit breakers to operate when installation is in island mode
- selecting RCDs/residual-current circuit breaker with overcurrent protection (RCBO) to operate when installation is in island mode
- drawing arrangements of 2-pole RCDs, 4-pole RCDs and combination RCDs
- obtaining evidence of compliance for the equipment selected
- # dividing installation into circuits
- selecting equipment for damp situations
- # coordination of protection devices and circuit wiring
- # selecting overcurrent protection devices, circuit breakers and RCDs/RCBOs
- selecting fuses, emergency controls, isolation devices, functional controls and shutdown devices
- selecting a device for fault current limiting protection
- documenting installation arrangement, specification for items selected and reasons for the selections made.
Knowledge evidence
- AS/NZS 3000 safety principles and deemed to comply requirements including:
- definition of terms
- direct contact with live parts
- indirect contact with live parts
- thermal effects of current
- overcurrent
- earth faults
- abnormal voltages
- spread of fire
- mechanical injury
- external influences
- fundamental principles of; installation design; selection and installation of equipment; means of compliance (including alterations, additions and repairs), and verification of compliance
- methods and devices that comply with industry standards for providing protection against indirect contact
- requirements for installation design and selection of equipment, including:
- compliant protection arrangements
- correct functioning
- compatibility with supply
- arrangement of circuits
- circuit and control arrangements, including:
- reason for dividing electrical installations into circuits
- factors to be considered in determining the number and type of circuits required for an installation
- daily and seasonal demand for lighting, power, heating and other loads in a given installation
- number and types of circuits required for a particular installation
- diagrams/schedules of circuits for given installations
- application and arrangements of separated extra-low voltage (SELV) and protected extra-low voltage (PELV) circuits, including earthing requirements and testing
- application and arrangement of an isolated supply
- hazards and risks in an electrical installation, including:
- effects on the human body of various levels of alternating current (a.c.) and direct current (d.c.) current and duration of current flow for various current paths
- risk of ignition of flammable materials due to the thermal effects of current or electric arcs in normal service of an electrical installation
- risk of injury from mechanical movement of electrically actuated equipment
- protection against direct contact (basic protection)
- acceptable methods
- use of ELV
- protection against indirect contact, including:
- indirect contact with live parts of an electrical installation may occur
- components of the ‘automatic disconnection of supply’ method of protection against indirect contact
- the terms ‘touch voltage’ and ‘touch current’
- the current path when a short circuit fault to exposed conductive parts of an appliance occurs
- protection against indirect contact is by the use of Class II equipment and by electrical separation
- additional protection by use of RCDs
- protection against indirect contact by use of ELV and electrical separation
- protection requirements for damp situations
- earthing, including:
- parts of an earthing system and the purpose of each, including the terms:
- earthed
- earthed situation
- earth electrode
- equipotential bonding
- MEN system
- protective earth-neutral (PEN) conductor
- main earthing conductor
- protective earthing (PE) conductor
- functional earthing
- MEN link
- typical arrangement for a MEN system and for a range of installation arrangements of PE conductors
- typical earthing arrangements for outbuildings
- alternate earthing systems only when required by local Regulatory Authorities (e.g. TT low voltage supply earthing system in dairy sheds in New Zealand)
- requirements for equipotential bonding in a range of installation situations
- protection against overload and short circuit current, including:
- overload current or fault currents in an electrical installation
- limitations of the use of overcurrent protection on current limited sources
- equivalent circuit of an earth fault-loop
- level of fault current possible at a given point in an installation from the fault-loop impedance and data from the local supply authority
- requirements for coordination of protection devices for discrimination and back-up protection, and between protective devices and conductors of an installation
- methods and devices that comply with industry standards for providing protection against the damaging effects of overload and fault current
- devices for automatic disconnection of supply, including:
- operating principles of thermal/magnet circuit breakers, common types of fuses and RCDs
- tripping characteristics of various types of circuit breakers
- time/current curves and fusing characteristics of various types of fuses
- tripping characteristics of various types of RCDs
- factors in a fault-loop that will affect the impedance of the circuit
- maximum impedance of an earth fault-loop to ensure operation of a protection device
- protection against over voltage and under voltage, including:
- causes of over and under voltage and how this may affect the electrical system
- methods for protection against over and under voltage
- control of an electrical installation and circuits, including:
- switch types, current and voltage ratings and ingress protection (IP) rating and where these apply
- switching requirements for isolation, emergency, mechanical maintenance and functional control
- control arrangement for complete installations with and without safety services and an alternative supply, including:
- d.c. polarity requirements
- correct rating of d.c. switches
- switchboards/distribution boards including:
- purpose, types and applications
- physical and circuit arrangements for whole current and current transformer metering
- physical and circuit arrangements of main switches, circuit protection devices, fault current limiters and metering equipment, and other distributor equipment
- switchgear types, ratings, characteristics and applications related to alternate supplies
- compliance requirements, including:
- location and access
- arc-fault protection
- identification
- construction suitability
- equipment marking
- wiring
- fire protection
- relevant WHS/OHS legislated requirements
- relevant workplace documentation
- relevant workplace policies and procedures.
Unit content sourced from training.gov.au — © Commonwealth of Australia, licensed under CC BY 4.0. Auditori is not affiliated with the Department of Employment and Workplace Relations.
See what you get before you start
Real, unedited Auditori output (RIIHAN201E shown), branded for a sample RTO:
Questions about assessing UEEEL0003
What does an assessment tool for UEEEL0003 need to cover?
To satisfy the Principles of Assessment and Rules of Evidence, an assessment for UEEEL0003 needs to address all 134 unit components: 3 elements with 12 performance criteria, 25 performance evidence requirements, 97 knowledge evidence requirements, and the foundation skills. A coverage matrix mapping each question and task to these components is what an auditor looks for.
How does Auditori generate an assessment tool for UEEEL0003?
Auditori pulls the current release of UEEEL0003 from training.gov.au and generates a complete package: candidate assessment, assessor guide with model answers and observation criteria, and a coverage matrix mapping every component. A suitably qualified person then reviews and approves the draft in a built-in workflow — consistent with ASQA's guidance on AI use in VET — before export as branded PDF and editable Word.
Is the first assessment tool really free?
Yes. Every new account includes one free credit — enough to generate the complete assessment tool for UEEEL0003 — with no card and no subscription required. After that it's pay-as-you-go per unit.
Can I check my existing UEEEL0003 assessment instead of generating a new one?
Yes — upload your existing assessment or learner guide and Auditori maps it against every element, performance criterion, PE and KE of UEEEL0003, showing exactly what's covered and what's missing. Mapping costs a quarter of a credit.
Related units
- UEEEL0001 — Apply compliance requirements to all aspects of electrical work
- UEEEL0002 — Apply currency of safe working practices and compliance verification of electrical installations
- UEEEL0004 — Carry out basic repairs to electrical components and equipment
- UEEEL0005 — Develop and connect electrical control circuits
- UEEEL0006 — Develop detailed and complex drawings for electrical systems using CAD systems
- UEEEL0007 — Develop detailed electrical drawings
- UEEEL0008 — Evaluate and modify low voltage heating equipment and controls
- UEEEL0009 — Evaluate and modify low voltage lighting circuits, equipment and controls
- UEEEL0010 — Evaluate and modify low voltage socket outlets circuits
- UEEEL0011 — Evaluate performance of low voltage electrical apparatus
- UEEEL0012 — Install low voltage wiring, appliances, switchgear and associated accessories
- UEEEL0014 — Isolate, test and troubleshoot low voltage electrical circuits